RBICAB Aluminium Armoured and Unarmoured Cables are high-quality electrical cables designed to provide reliable power transmission for industrial, commercial, and residential applications. These cables are engineered for efficiency, safety, and long-term performance, offering excellent conductivity with aluminium conductors that are lightweight yet highly durable.
RBICAB Armoured Aluminium Cables feature a protective metallic layer, typically made of galvanized steel wires or strips, to shield the cable from mechanical damage, impact, rodents, and external stresses. This makes them ideal for underground, outdoor, or industrial installations where extra protection is required.
RBICAB Unarmoured Aluminium Cables, on the other hand, provide flexibility and easy installation in controlled environments where mechanical protection is not critical. These are commonly used in indoor wiring, cable trays, building electrical systems, and overhead installations.
Compliant with international standards like IEC, IS, and BS, RBICAB Aluminium Armoured and Unarmoured Cables ensure safety, reliability, and long service life. They are widely used in power distribution networks, industrial plants, renewable energy systems, commercial complexes, and infrastructure projects. Their robust design ensures operational stability, making them a preferred choice for both developers and end-users who require safe and efficient electricity transmission in varied conditions.
| Feature / Application | Details |
|---|---|
| Conductor Material | High-purity aluminium for lightweight, excellent conductivity, and efficient power transmission |
| Cable Type | Armoured for mechanical protection (galvanized steel or aluminium) or unarmoured for indoor flexibility |
| Insulation Material | PVC, XLPE, or other high-performance compounds resistant to heat, moisture, chemicals, and fire |
| Primary Uses | Power distribution, industrial plants, renewable energy systems, commercial complexes, and infrastructure projects |
| Mechanical Protection | Armoured cables protect against mechanical stress, impact, rodent attacks, and harsh environmental conditions |
| Installation Environment | Indoor wiring, cable trays, panels, overhead installations, and outdoor underground deployments |
| Durability | High mechanical strength, corrosion resistance, and long service life |
| Standards Compliance | Manufactured as per IEC, IS, BS, and other international standards |
| Performance | Ensures safe, efficient, and reliable power transmission with minimal energy loss |
| Nominal Size of Conductor | Form of Conductor Circular | Nominal Thickness of XLPE Insulation For U/A | Minimum Thickness of PVC Inner Sheath | Unarmoured Cable | Nominal Thickness of XLPE Insulation For Armoured Cable | Formed Wire / Strip Armoured Cable | Round Wire Armoured Cable | Current Rating (Amps) | Normal Delivery Length (mtrs) | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight of cable | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | Nominal Dimension of Aluminium Round Wire | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | In Ground | In Air | |||||||
| Sq.mm | mm | mm | mm | mm | mm | Kgs./Km | mm | mm | mm | mm | Kgs./Km | mm | mm | mm | Kgs./Km | Amps. | Amps. | Mtrs. |
| 4 | Solid | 0.70 | -NA- | 1.80 | 7.50 | 60 | - | - | - | - | - | - | - | - | - | 43 | 38 | 1000 |
| 4 | Stranded | 0.70 | -NA- | 1.80 | 8 | 65 | - | - | - | - | - | - | - | - | - | 43 | 38 | 1000 |
| 6 | Solid | 0.70 | -NA- | 1.80 | 8 | 70 | - | - | - | - | - | - | - | - | - | 55 | 50 | 1000 |
| 6 | Standard | 0.70 | -NA- | 1.80 | 8.50 | 75 | - | - | - | - | - | - | - | - | - | 55 | 50 | 1000 |
| 10 | Solid | 0.70 | -NA- | 1.80 | 9 | 80 | 1 | - | - | - | - | - | - | - | - | 69 | 64 | 1000 |
| 10 | Standard | 0.70 | -NA- | 1.80 | 9.50 | 90 | 1 | - | - | - | - | - | - | - | - | 69 | 64 | 1000 |
| 16 | Standard | 0.70 | -NA- | 1.80 | 10 | 115 | 1 | - | - | - | - | 1.40 | 1.24 | 13 | 193.30 | 69 | 64 | 1000 |
| 25 | Standard | 0.90 | -NA- | 1.80 | 12 | 155 | 1.20 | - | - | - | - | 1.40 | 1.24 | 14 | 250 | 115 | 112 | 1000 |
| 35 | Standard | 0.90 | -NA- | 1.80 | 13 | 180 | 1.20 | - | - | - | - | 1.40 | 1.24 | 15 | 293.40 | 137 | 137 | 1000 |
| 50 | Stranded | 1 | -NA- | 1.80 | 14 | 240 | 1.30 | - | - | - | - | 1.40 | 1.24 | 17 | 353.5 | 161 | 165 | 1000 |
| 70 | Stranded | 1.10 | -NA- | 1.80 | 16 | 310 | 1.40 | - | - | - | - | 1.40 | 1.24 | 19 | 443 | 198 | 209 | 1000 |
| 95 | Stranded | 1.10 | -NA- | 1.80 | 17.50 | 385 | 1.40 | 4x0.80 | 1.40 | 18.60 | 498.81 | 1.60 | 1.40 | 20.20 | 572.30 | 243 | 264 | 1000 |
| 120 | Stranded | 1.20 | -NA- | 1.80 | 19 | 470 | 1.50 | 4x0.80 | 1.40 | 20.40 | 606.34 | 1.60 | 1.40 | 23.50 | 678.74 | 276 | 308 | 1000 |
| 150 | Stranded | 1.40 | -NA- | 2 | 21.50 | 600 | 1.70 | 4x0.80 | 1.40 | 23 | 716.08 | 1.60 | 1.40 | 24.50 | 795.36 | 308 | 350 | 1000 |
| 185 | Stranded | 1.60 | -NA- | 2 | 23.50 | 710 | 1.90 | 4x0.80 | 1.40 | 25 | 866.86 | 1.60 | 1.40 | 26.50 | 947.06 | 349 | 406 | 1000 |
| 240 | Stranded | 1.70 | -NA- | 2 | 26 | 900 | 2 | 4x0.80 | 1.40 | 26.60 | 1055.79 | 1.60 | 1.40 | 29 | 1147.15 | 404 | 480 | 1000 |
| 300 | Stranded | 1.80 | -NA- | 2 | 28.50 | 1158 | 2.10 | 4x0.80 | 1.56 | 29.60 | 1294.16 | 1.60 | 1.56 | 31.50 | 1389.30 | 454 | 451 | 1000 |
| 400 | Stranded | 2 | -NA- | 2.20 | 33 | 1385 | 2.40 | 4x0.80 | 1.56 | 33.20 | 1624.42 | 2 | 1.56 | 36.50 | 1813.29 | 518 | 647 | 500 |
| 500 | Stranded | 2.20 | -NA- | 2.20 | 36 | 1650 | 2.60 | 4x0.80 | 1.56 | 36.70 | 1997.06 | 2 | 1.56 | 39.50 | 2213.57 | 588 | 751 | 500 |
| 630 | Stranded | 2.40 | -NA- | 2.20 | 40 | 2100 | 2.80 | 4x0.80 | 1.72 | 40.50 | 2469.72 | 2 | 1.72 | 43 | 2698.20 | 663 | 868 | 500 |
| 800 | Stranded | 2.60 | -NA- | 2.40 | 43.70 | 2730 | 3.10 | 4x0.80 | 1.72 | 46.50 | 2986.96 | 2 | 1.88 | 47.90 | 3279.82 | 740 | 992 | 550 |
| 1000 | Stranded | 2.80 | -NA- | 2.60 | 49.20 | 3350 | 3.30 | 4x0.80 | 1.88 | 50.60 | 3742.01 | 2.50 | 2.04 | 54.37 | 4220.31 | 812 | 1117 | 500 |
| Nominal Size of Cable (Sq. mm) |
3, 3.5 & 4 Core PVC Insulated & Sheathed Cables as per IS-1554 (Part-1) 1988 |
3, 3.5 & 4 Core XLPE Insulated & Sheathed Cables as per IS-7098 (Part-1) 1988 |
||||
|---|---|---|---|---|---|---|
| In Ground | In Air | Approx Voltage Drop | In Ground | In Air | Approx Voltage Drop | |
| Sq.mm | Amp | Amp | Mv/amp/mtr | Amp | Amp | Mv/amv/mtr |
| 16 | 61 | 52 | 4.00 | 74 | 69 | 4.20 |
| 25 | 78 | 70 | 2.50 | 94 | 93 | 2.70 |
| 35 | 94 | 85 | 1.80 | 114 | 114 | 1.90 |
| 50 | 111 | 104 | 1.30 | 134 | 175 | 1.40 |
| 70 | 136 | 131 | 1.00 | 167 | 175 | 0.99 |
| 95 | 163 | 156 | 0.68 | 197 | 216 | 0.72 |
| 120 | 185 | 186 | 0.54 | 223 | 249 | 0.58 |
| 150 | 206 | 212 | 0.43 | 249 | 284 | 0.48 |
| 185 | 234 | 245 | 0.38 | 282 | 329 | 0.41 |
| 240 | 271 | 291 | 0.28 | 327 | 392 | 0.31 |
| 300 | 305 | 335 | 0.25 | 369 | 452 | 0.29 |
| 400 | 348 | 390 | 0.20 | 420 | 526 | 0.21 |
| Nominal Size of Conductor | Minimum no. of wires | Max D.C. Resistance at 20°C | A.C. Resistance at 90°C | |||||
|---|---|---|---|---|---|---|---|---|
| Non Compacted | Compacted | Plain Copper | Aluminium | Plain Copper | Aluminium | |||
| Round/Shaped | ||||||||
| Sq.mm | CU. | ALU. | CU. | ALU. | Ohm/Km | Ohm/Km | Ohm/Km | Ohm/Km |
| 1.5* | 3 | 3 | - | - | 12.10 | 18.1 | 15.50 | 23.17 |
| 2.5* | 3 | 3 | - | - | 7.41 | 12.1 | 9.48 | 15.50 |
| 4* | 7 | 3 | - | - | 4.61 | 7.41 | 5.90 | 9.48 |
| 6* | 7 | 3 | - | - | 3.08 | 4.61 | 3.94 | 5.90 |
| 10* | 7 | 7 | 6 | - | 1.83 | 3.08 | 2.34 | 3.94 |
| 16 | 7 | 7 | 6 | 6 | 1.15 | 1.91 | 1.47 | 2.44 |
| 25 | 7 | 7 | 6 | 6 | 0.727 | 1.20 | 0.93 | 1.54 |
| 35 | 7 | 7 | 6 | 6 | 0.524 | 0.868 | 0.671 | 1.11 |
| 50 | 19 | 19 | 6 | 6 | 0.387 | 0.641 | 0.495 | 0.82 |
| 70 | 19 | 19 | 12 | 12 | 0.268 | 0.443 | 0.343 | 0.567 |
| 95 | 19 | 19 | 15 | 15 | 0.193 | 0.32 | 0.247 | 0.410 |
| 120 | 37 | 37 | 18 | 15 | 0.153 | 0.253 | 0.196 | 0.324 |
| 150 | 37 | 37 | 18 | 15 | 0.124 | 0.206 | 0.159 | 0.264 |
| 185 | 37 | 37 | 30 | 30 | 0.0991 | 0.164 | 0.127 | 0.210 |
| 240 | 61 | 37 | 34 | 30 | 0.0754 | 0.125 | 0.0965 | 0.160 |
| 300 | 61 | 61 | 34 | 30 | 0.0601 | 0.100 | 0.0769 | 0.128 |
| 400 | 61 | 61 | 53 | 53 | 0.047 | 0.0778 | 0.0602 | 0.100 |
| 500 | 61 | 61 | 53 | 53 | 0.0366 | 0.0605 | 0.0468 | 0.0774 |
| 630 | 91 | 91 | 53 | 53 | 0.0283 | 0.0469 | 0.0362 | 0.0600 |
| 800 | 91 | 91 | 53 | 53 | 0.0221 | 0.0367 | 0.0283 | 0.0470 |
| Nominal Size of Conductor | Form of Conductor Circular Shaped O/Q | Nominal Thickness of XLPE Insulation For U/A | Minimum Thickness of PVC Inner Sheath | Unarmoured Cable | Formed Wire / Strip Armoured Cable | Round Wire Armoured Cable | Current Rating. * | *Normal Delivery Length | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight of cable | Nominal Dimension of Aluminium Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | Nominal Dimension of Aluminium Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | In Ground | In Air | |||||
| Sq.mm | mm | mm | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | Amps. | Amps. | Mtrs. |
| 4 | Solid o | 0.70 | 0.30 | 1.80 | 12.50 | 140 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 14.50 | 400 | 42 | 38 | 1000 |
| 4 | Stranded o | 0.70 | 0.30 | 1.80 | 13 | 150 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 15.50 | 430 | 42 | 38 | 1000 |
| 6 | Solid o | 0.70 | 0.30 | 1.80 | 13.50 | 170 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 15.50 | 470 | 55 | 50 | 1000 |
| 6 | Stranded o | 0.70 | 0.30 | 1.80 | 14 | 180 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 16.50 | 485 | 55 | 50 | 1000 |
| 10 | Solid o | 0.70 | 0.30 | 1.80 | 15 | 205 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 17 | 545 | 68 | 64 | 1000 |
| 10 | Stranded o | 0.70 | 0.30 | 1.80 | 16 | 225 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 18 | 565 | 68 | 64 | 1000 |
| 16 | Stranded Q | 0.70 | 0.30 | 1.80 | 14 | 225 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.20 | 17 | 480.16 | 89 | 83 | 1000 |
| 25 | Stranded Q | 0.90 | 0.30 | 2 | 17 | 330 | 4x0.80 | 1.40 | 18.50 | 509.13 | 1.60 | 1.40 | 20 | 671.84 | 114 | 109 | 1000 |
| 35 | Stranded Q | 0.90 | 0.30 | 2 | 19 | 410 | 4x0.80 | 1.40 | 20 | 605.51 | 1.60 | 1.40 | 22 | 775.55 | 136 | 133 | 1000 |
| 50 | Stranded Q | 1 | 0.30 | 2 | 21 | 510 | 4x0.80 | 1.40 | 22.50 | 753.28 | 1.60 | 1.40 | 24 | 937.97 | 161 | 162 | 1000 |
| 70 | Stranded Q | 1.10 | 0.30 | 2 | 23 | 675 | 4x0.80 | 1.56 | 22.50 | 971 | 1.60 | 1.56 | 27 | 1188.85 | 197 | 204 | 1000 |
| 95 | Stranded Q | 1.10 | 0.40 | 2.20 | 26.50 | 900 | 4x0.80 | 1.56 | 28 | 1204.30 | 2 | 1.56 | 28.68 | 1572.78 | 235 | 251 | 1000 |
| 120 | Stranded Q | 1.20 | 0.40 | 2.20 | 28.50 | 1050 | 4x0.80 | 1.56 | 30.50 | 1408.20 | 2 | 1.56 | 33 | 1849.49 | 266 | 287 | 500 |
| 150 | Stranded Q | 1.40 | 0.40 | 2.20 | 32 | 1215 | 4x0.80 | 1.72 | 31.79 | 1690.20 | 2 | 1.72 | 36 | 2182.96 | 296 | 328 | 500 |
| 185 | Stranded Q | 1.60 | 0.50 | 2.40 | 35.50 | 1510 | 4x0.80 | 1.72 | 34.95 | 2025.90 | 2 | 1.88 | 37.70 | 2597.60 | 335 | 379 | 500 |
| 240 | Stranded Q | 1.70 | 0.50 | 2.60 | 39.50 | 1900 | 4x0.80 | 1.88 | 38.69 | 2500.60 | 2.50 | 2.04 | 45 | 3418.52 | 385 | 448 | 500 |
| 300 | Stranded Q | 1.80 | 0.60 | 2.80 | 43.50 | 2360 | 4x0.80 | 2.04 | 42.53 | 2992.20 | 2.50 | 2.20 | 46.22 | 4019.07 | 432 | 513 | 500 |
| 400 | Stranded Q | 2 | 0.60 | 3 | 49 | 3100 | 4x0.80 | 2.36 | 48.24 | 3790.21 | 2.50 | 2.36 | 51.61 | 4880.51 | 487 | 593 | 500 |
| 500 | Stranded Q | 2.20 | 0.70 | 3.40 | 55.50 | 4000 | 4x0.80 | 2.52 | 56.50 | 5000 | 3.15 | 2.68 | 61.50 | 7000 | 548 | 683 | 500 |
| 630 | Stranded | 2.40 | 0.70 | 3.60 | 61.50 | 5000 | 4x0.80 | 2.68 | 62.50 | 6050 | 3.15 | 2.84 | 67.50 | 8560 | 612 | 784 | 500 |
| Nominal Size of Conductor | Form of Conductor Circular Shaped O/zs | Nominal Thickness of XLPE Insulation | Minimum Thickness of PVC Inner Sheath | Unarmoured Cable | Formed Wire / Strip Armoured Cable | Round Wire Armoured Cable | Current Rating. * | *Normal Delivery Length | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight of cable | Nominal Dimension of GI Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | Nominal Dimension of GI Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | In Ground | In Air | |||||
| Sq.mm | mm | mm | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | Amps. | Amps. | Mtrs. |
| 4 | Solid o | 0.70 | 0.30 | 1.80 | 14 | 140 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 15 | 460 | 35 | 32 | 1000 |
| 4 | Stranded o | 0.70 | 0.30 | 1.80 | 15.50 | 160 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 16 | 510 | 35 | 32 | 1000 |
| 6 | Solid o | 0.70 | 0.30 | 1.80 | 15.50 | 170 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 16 | 530 | 46 | 42 | 1000 |
| 6 | Stranded ^ | 0.70 | 0.30 | 1.80 | 16 | 190 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 17 | 580 | 46 | 42 | 1000 |
| 10 | Solid ^ | 0.70 | 0.30 | 1.80 | 17 | 220 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 18 | 640 | 57 | 54 | 1000 |
| 10 | Stranded o | 0.70 | 0.30 | 1.80 | 18 | 230 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 18.50 | 680 | 57 | 54 | 1000 |
| 16 | Stranded ^ | 0.70 | 0.30 | 1.80 | 16.20 | 310 | 4x0.80 | 1.24 | 16.80 | 487.60 | 1.60 | 1.40 | 19 | 648.40 | 74 | 69 | 1000 |
| 25 | Stranded ^ | 0.90 | 0.30 | 2 | 19.50 | 460 | 4x0.80 | 1.40 | 20.10 | 670.70 | 1.60 | 1.40 | 21.70 | 863.30 | 95 | 93 | 1000 |
| 35 | Stranded ^ | 0.90 | 0.30 | 2 | 21.50 | 573.80 | 4x0.80 | 1.40 | 22 | 800.60 | 1.60 | 1.40 | 23.60 | 1015.80 | 114 | 114 | 1000 |
| 50 | Stranded ^ | 1 | 0.30 | 2 | 24.50 | 700 | 4x0.80 | 1.40 | 24.80 | 993.7 | 1.60 | 1.56 | 26.80 | 1259.60 | 134 | 138 | 1000 |
| 70 | Stranded ^ | 1.10 | 0.40 | 2.20 | 28 | 990 | 4x0.80 | 1.56 | 28.50 | 1299.60 | 2 | 1.56 | 30.90 | 1740.10 | 164 | 175 | 500 |
| 95 | Stranded ^ | 1.10 | 0.40 | 2.20 | 30.80 | 1250 | 4x0.80 | 1.56 | 31.30 | 1603 | 2 | 1.56 | 33.70 | 2117 | 197 | 216 | 500 |
| 120 | Stranded ^ | 1.20 | 0.40 | 2.20 | 33.80 | 1525 | 4x0.80 | 1.56 | 34.30 | 1914.10 | 2 | 1.72 | 37 | 2506.50 | 223 | 249 | 500 |
| 150 | Stranded ^ | 1.40 | 0.50 | 2.40 | 37.90 | 1895.90 | 4x0.80 | 1.72 | 38.30 | 2100 | 2 | 1.88 | 41.10 | 2988.80 | 249 | 284 | 500 |
| 185 | Stranded ^ | 1.60 | 0.50 | 2.60 | 42 | 2349.30 | 4x0.80 | 1.88 | 42.30 | 2500 | 2.50 | 2.04 | 46 | 3867.40 | 282 | 329 | 500 |
| 240 | Stranded ^ | 1.70 | 0.60 | 2.80 | 46.90 | 2981.40 | 4x0.80 | 2.04 | 47.20 | 3459.80 | 2.50 | 2.20 | 50.90 | 4677.30 | 327 | 392 | 500 |
| 300 | Stranded ^ | 1.80 | 0.60 | 3 | 51.50 | 3615.80 | 4x0.80 | 2.20 | 51.80 | 4150.20 | 2.50 | 2.36 | 55.45 | 5491.40 | 369 | 452 | 500 |
| 400 | Stranded ^ | 2 | 0.70 | 3.20 | 58.60 | 4650.10 | 4x0.80 | 2.52 | 58.50 | 5250.60 | 3.15 | 2.68 | 64 | 7401.40 | 420 | 526 | 500 |
| 500 | Stranded ^ | 2.20 | 0.70 | 3.60 | 66 | 6000 | 4x0.80 | 2.68 | 67 | 6900 | 3.15 | 2.84 | 73 | 9550 | 478 | 612 | 250 |
| 630 | Stranded ^ | 2.40 | 0.70 | 3.80 | 72 | 7550 | 4x0.80 | 2.84 | 73 | 8700 | 4 | 3 | 78 | 12500 | 542 | 712 | 250 |
| Nominal Size of Conductor | Form of Conductor Circular Shaped | Nominal Thickness of XLPE Insulation Main / Neutral | Minimum Thickness of PVC Inner Sheath | Unarmoured Cable | Formed Wire / Strip Armoured Cable | Round Wire Armoured Cable | Current Rating. * | *Normal Delivery Length | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight of cable | Nominal Dimension of GI Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | Nominal Dimension of GI Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | In Ground | In Air | ||||||
| Sq.mm | mm | mm | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | Amps. | Amps. | Mtrs. | |
| 25/16 | Stranded | 0.90 | 0.70 | 0.30 | 2 | 21.30 | 525 | 4×0.80 | 1.40 | 21.90 | 733 | 1.60 | 1.40 | 23.60 | 971 | 95 | 93 | 1000 |
| 35/16 | Stranded | 0.90 | 0.70 | 0.30 | 2 | 23.60 | 625 | 4×0.80 | 1.40 | 24.20 | 886 | 1.60 | 1.40 | 25.80 | 1139 | 114 | 114 | 1000 |
| 50/25 | Stranded | 1 | 0.90 | 0.40 | 2 | 26.80 | 800 | 4×0.80 | 1.40 | 27.40 | 1113 | 1.60 | 1.56 | 29.50 | 1419 | 134 | 138 | 1000 |
| 70/35 | Stranded | 1.10 | 0.90 | 0.40 | 2.20 | 31 | 1100 | 4×0.80 | 1.56 | 31.50 | 1451 | 2 | 1.56 | 34 | 1989 | 164 | 175 | 500 |
| 95/50 | Stranded | 1.20 | 1.00 | 0.40 | 2.20 | 34.30 | 1400 | 4×0.80 | 1.56 | 34.80 | 1796 | 2 | 1.56 | 37.20 | 2382 | 197 | 216 | 500 |
| 120/70 | Stranded | 1.20 | 1.10 | 0.40 | 2.20 | 37.50 | 1650 | 4×0.80 | 1.72 | 38.50 | 2199 | 2 | 1.72 | 41 | 2800 | 223 | 249 | 500 |
| 150/70 | Stranded | 1.40 | 1.10 | 0.50 | 2.40 | 41 | 2000 | 4×0.80 | 1.72 | 42 | 2579 | 2 | 1.88 | 45 | 3350 | 249 | 282 | 500 |
| 185/95 | Stranded | 1.60 | 1.10 | 0.50 | 2.60 | 46.50 | 2550 | 4×0.80 | 1.88 | 47.20 | 3166 | 2.50 | 2.04 | 50 | 4381 | 282 | 329 | 500 |
| 240/120 | Stranded | 1.70 | 1.20 | 0.60 | 2.80 | 52.50 | 3200 | 4×0.80 | 2.04 | 52.70 | 3913 | 2.50 | 2.20 | 56 | 5313 | 327 | 392 | 500 |
| 300/150 | Stranded | 1.80 | 1.40 | 0.60 | 3 | 56 | 4000 | 4×0.80 | 2.20 | 57 | 4716 | 2.50 | 2.50 | 56 | 6254 | 369 | 452 | 250 |
| 400/185 | Stranded | 2 | 1.70 | 0.70 | 3.40 | 64 | 5250 | 4×0.80 | 2.52 | 65 | 6000 | 3.15 | 2.50 | 61 | 8300 | 420 | 526 | 500 |
| 500/240 | Stranded | 2.20 | 1.70 | 0.70 | 3.60 | 72.50 | 6500 | 4×0.80 | 2.68 | 73.50 | 7400 | 3.15 | 2.84 | 77 | 9880 | 478 | 612 | 250 |
| Nominal Size of Conductor | Form of Conductor Circular Shaped | Nominal Thickness of XLPE Insulation | Minimum Thickness of PVC Inner Sheath | Unarmoured Cable | Formed Wire / Strip Armoured Cable | Round Wire Armoured Cable | Current Rating. * | *Normal Delivery Length | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight of cable | Nominal Dimension of GI Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | Nominal Dimension of GI Flat Strip | Minimum Thickness of PVC Outer Sheath | Approx Overall Diameter Of Cable | Approx Weight Of Cable | In Ground | In Air | |||||
| Sq.mm | mm | mm | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | mm | mm | mm | Kgs/Km | Amps. | Amps. | Mtrs. |
| 4 | Solid o | 0.70 | 0.30 | 1.80 | 13.50 | 160 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 15.30 | 413 | 35 | 32 | 1000 |
| 4 | Stranded o | 0.70 | 0.30 | 1.80 | 14.20 | 180 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 16 | 435 | 35 | 32 | 1000 |
| 6 | Solid o | 0.70 | 0.30 | 1.80 | 14.70 | 200 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 16.50 | 473 | 46 | 42 | 1000 |
| 6 | Stranded o | 0.70 | 0.30 | 1.80 | 15.50 | 215 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.24 | 17.30 | 506 | 46 | 42 | 1000 |
| 10 | Solid o | 0.70 | 0.30 | 1.80 | 16.60 | 250 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.40 | 18.60 | 592 | 57 | 54 | 1000 |
| 10 | Stranded o | 0.70 | 0.30 | 1.80 | 17.50 | 260 | -NA- | -NA- | -NA- | -NA- | 1.40 | 1.40 | 19.80 | 633 | 57 | 54 | 1000 |
| 16 | Stranded | 0.70 | 0.30 | 1.80 | 17.80 | 350 | 4*0.80 | 1.40 | 20 | 624.50 | 1.60 | 1.40 | 21 | 795 | 74 | 69 | 1000 |
| 25 | Stranded | 0.90 | 0.30 | 2 | 21 | 550 | 4*0.80 | 1.40 | 23 | 828.50 | 1.60 | 1.40 | 25 | 1062 | 95 | 93 | 500 |
| 35 | Stranded | 0.90 | 0.30 | 2 | 23.50 | 680 | 4*0.80 | 1.40 | 25 | 1015.50 | 1.60 | 1.40 | 26.50 | 1259 | 114 | 114 | 500 |
| 50 | Stranded | 1 | 0.30 | 2 | 26 | 875 | 4*0.80 | 1.56 | 28 | 1275 | 1.60 | 1.56 | 29.50 | 1581 | 134 | 138 | 500 |
| 70 | Stranded | 1.10 | 0.40 | 2.20 | 30.50 | 1200 | 4*0.80 | 1.56 | 32 | 1656.40 | 2 | 1.56 | 34 | 2175 | 164 | 175 | 500 |
| 95 | Stranded | 1.10 | 0.40 | 2.20 | 33.50 | 1530 | 4*0.80 | 1.56 | 35 | 2041.90 | 2 | 1.72 | 38 | 2695 | 197 | 216 | 500 |
| 120 | Stranded | 1.20 | 0.50 | 2.40 | 37.50 | 1850 | 4*0.80 | 1.72 | 39 | 2442.50 | 2 | 1.88 | 42 | 3241 | 223 | 249 | 500 |
| 150 | Stranded | 1.40 | 0.50 | 2.60 | 42 | 2280 | 4*0.80 | 1.88 | 43 | 2929.90 | 2.50 | 2.04 | 47 | 4167 | 249 | 284 | 500 |
| 185 | Stranded | 1.60 | 0.50 | 2.80 | 46.50 | 2800 | 4*0.80 | 2.04 | 48 | 3563.10 | 2.50 | 2.20 | 52 | 4928 | 282 | 329 | 500 |
| 240 | Stranded | 1.70 | 0.60 | 3 | 52.50 | 3700 | 4*0.80 | 2.20 | 54 | 4464.30 | 2.50 | 2.36 | 57.50 | 5998 | 327 | 292 | 500 |
| 300 | Stranded | 1.80 | 0.70 | 3.20 | 58 | 4600 | 4*0.80 | 2.36 | 59.50 | 5359.50 | 3.15 | 2.52 | 64.50 | 7722 | 369 | 452 | 500 |
| 400 | Stranded | 2 | 0.70 | 3.60 | 65.50 | 6000 | 4*0.80 | 2.68 | 66.50 | 6749.30 | 3.15 | 2.84 | 71.50 | 9487 | 420 | 526 | 500 |
D-18, SITE-3, Meerut Road Industrial Area, UPSIDC, Ghaziabad, Uttar Pradesh - 201003 (INDIA)