RBICAB PVC Insulated Power Cables are versatile electrical cables designed for efficient and safe power distribution across industrial, commercial, and residential networks. These cables utilize high-quality PVC (Polyvinyl Chloride) insulation, known for its excellent dielectric strength, durability, and protective qualities, surrounding high-conductivity copper or aluminium conductors.
The PVC insulation provides robust protection against electrical leakage, short circuits, and environmental factors such as heat, moisture, and mild chemical exposure. This makes the cables suitable for a broad spectrum of applications, including fixed installations in buildings, industrial plants, power stations, and outdoor systems when installed within appropriate protective conduits or trunking.
Manufactured to meet international standards (IEC, IS, and equivalents), these cables are available in various configurations, including armoured and unarmoured, single-core and multi-core, to suit specific voltage levels (up to 1100V) and load requirements. They ensure reliable performance, thermal stability, and long-term operational safety.
Key advantages include reliable electrical insulation, good thermal and chemical resistance, compliance with safety standards, versatility for multiple installation types, and a proven track record in global electrical infrastructure.
Feature / Application | Details |
|---|---|
Conductor Material | High-purity copper or aluminium for excellent conductivity |
Cable Type | Armoured for mechanical protection; Unarmoured for indoor installations |
Insulation | PVC insulation for heat, moisture, and chemical resistance |
Voltage Rating | Suitable for low and medium voltage installations |
Current Carrying Capacity | As per conductor size and installation method |
Installation | Indoor, outdoor, industrial, residential, and commercial wiring |
Mechanical Protection | Armoured version protects against impact, rodents, and harsh conditions |
Standards Compliance | Manufactured as per IEC, IS, or equivalent standards |
Applications | Power distribution, lighting circuits, industrial plants, residential and commercial buildings |
Nominal Size of Cable | 3, 3.5 & 4 Core PVC Insulated & Sheathed Cables | ||
|---|---|---|---|
In Ground | In Air | Approx Voltage Drop | |
Amp | Amp | Mv/amp/mtr | |
16 | 61 | 52 | 4.00 |
25 | 78 | 70 | 2.50 |
35 | 94 | 85 | 1.80 |
50 | 111 | 104 | 1.30 |
70 | 136 | 131 | 1.00 |
95 | 163 | 156 | 0.68 |
120 | 185 | 186 | 0.54 |
150 | 206 | 212 | 0.43 |
185 | 234 | 245 | 0.38 |
240 | 271 | 291 | 0.28 |
300 | 305 | 335 | 0.25 |
400 | 348 | 390 | 0.20 |
Nominal Size | PVC Insulated | |
|---|---|---|
Copper | Aluminium | |
1.5 | 0.173 | - |
2.5 | 0.283 | - |
4 | 0.46 | 0.303 |
6 | 0.69 | 0.455 |
10 | 1.15 | 0.758 |
16 | 1.84 | 1.21 |
25 | 2.88 | 1.90 |
35 | 4.03 | 2.65 |
50 | 5.75 | 3.79 |
70 | 8.05 | 5.31 |
95 | 10.90 | 7.20 |
120 | 13.80 | 9.10 |
150 | 17.30 | 11.40 |
185 | 21.30 | 14.02 |
240 | 27.60 | 18.20 |
300 | 34.50 | 22.80 |
400 | 46 | 30.40 |
500 | 57.50 | 38 |
630 | 72.50 | 47.25 |
800 | 92 | 60 |
1000 | 115.00 | 75 |
D-18, Site-3, Meerut Road Industrial Area, UPSIDC, Ghaziabad, Uttar Pradesh 201003 (INDIA)