Photovoltaic DC Cables Supplier In Deoria

RBICAB Photovoltaic DC Cables are purpose-built for solar energy systems, delivering optimized performance in photovoltaic power transmission from generation to conversion points. These cables employ oxygen-free, tinned copper conductors to ensure minimal resistance and maximum current carrying capacity.

Engineered for photovoltaic environments, these cables feature advanced polymer insulation with exceptional UV resistance, flame retardancy, and weatherability. The robust construction withstands ozone, temperature extremes, and mechanical stresses common in solar installations.

With excellent flexibility and tensile strength, RBICAB Photovoltaic DC Cables simplify installation in complex array configurations while maintaining reliability in fixed installations. Their design accommodates expansion/contraction cycles and prolonged outdoor exposure without performance degradation.

Meeting stringent IEC and TUV standards for photovoltaic applications, these cables provide the safety margins, durability, and efficiency required for modern solar power systems of all scales and configurations.

CONSTRUCTION CHARACTERISTICS

  • Conductor: Electrolytic Multi Stranded Tinned Copper Conductor Flexible (As per IEC 60228) Class 5.

  • Insulation: Crosslinked Halogen Free & Flame Retardant Insulation.

  • Sheath: Crosslinked Halogen Free & Flame Retardant Sheath (in Black/Blue/Red Colour).

Electrical Characteristics

Parameter

Value

Rated Voltage

0.6/1 kV AC

Rated DC Voltage

1.5 kV

Maximum DC Voltage

1.8 kV

Maximum AC Voltage

0.7/1.2 kV

Working Voltage

DC 1000 V

Insulation Resistance

1000 MΩ-km

Spark Test

6000 Vac (8400 Vdc)

Voltage Withstand

6500 V for 5 min (EN50395)

Ampacity

As per PV system requirements

Current Carrying Capacity And Dimension

Area(Sq. mm)

Conductor Resistance(Ω/km @20°C, Max)

Current carrying capacity (Amp)

Overall Diameter in mm (approx.)

Single cable(In air)

Single cable(On surface )

Two cable(On surface)

2Pfg 1169(As per IS standard)

2Pfg 1990 and EN 50618(As per IS standard)

2.5

8.21

41

39

33

5.0

6.5

4

5.09

55

52

44

5.5

7.0

6

3.39

70

67

57

6.0

7.5

10

1.96

98

93

79

7.0

8.6

16

1.24

132

125

107

8.0

9.9

25

0.795

176

167

142

10.5

11.4

35

0.565

218

207

176

11.5

12.5

Need special / Customise cables according to your requirements? We Provide a Variety of Solutions – Contact Us Now!
SOLAR DC CABLES FROM PV MODULE TO ARRAY JUNCTION BOX
( AS PER TUV SPECIFICATION - EN 50618 : 2014 )

Area(sq. mm)

INSULATION Thickness (mm)

SHEATH Thickness(mm)

Overall Diameter(mm)

Tolerance on Diameter

Tinned Copper Maximum Resistance at 20°C(ohms - Ω / km)

Current Carrying Capacity(Single cable in Air) Amps

1.5

0.7

0.8

4.8

+/- 0.4

13.700

30

2.5

0.7

0.8

5.2

+/- 0.4

8.210

41

4

0.7

0.8

5.8

+/- 0.4

5.090

55

6

0.7

0.8

6.4

+/- 0.4

3.390

70

Need special / Customise cables according to your requirements? We Provide a Variety of Solutions – Contact Us Now!
SOLAR DC CABLES FROM ARRAY JUNCTION BOX TO MAIN JUNCTION BOX & MJB TO INVERTER
( AS PER TUV SPECIFICATION - EN 50618 : 2014 )

Area(sq. mm)

INSULATION Thickness(mm)

SHEATH Thickness(mm)

Overall Diameter(mm)

Tolerance on Diameter

Tinned Copper Maximum Resistance at 20°C(ohms - Ω / km)

Current Carrying Capacity(Single cable in Air) Amps

10

0.7

0.8

7.3

+/-0.4

1.950

98

16

0.7

0.9

8.6

+/-0.4

1.240

132

25

0.9

1.0

10.4

+/-0.4

0.795

176

35

0.9

1.1

11.8

+/-0.4

0.565

218

50

1.0

1.2

13.8

+/-0.4

0.393

276

70

1.1

1.2

15.6

+/-0.4

0.277

347

95

1.1

1.3

17.7

+/-0.4

0.210

416

120

1.2

1.3

19.5

+/-0.5

0.164

488

150

1.4

1.4

21.6

+/-0.5

0.132

566

185

1.6

1.6

24.2

+/-0.5

0.108

644

240

1.7

1.7

27.1

+/-0.5

0.0817

775

Need special / Customise cables according to your requirements? We Provide a Variety of Solutions – Contact Us Now!
Go Back Top