RBICAB Low Voltage PVC Cables are specifically designed for electrical systems operating at voltages up to 1100V, making them the ideal choice for the final distribution of power to end-point devices, machinery, and appliances. These cables ensure safe and efficient energy delivery in domestic, commercial, and industrial low-voltage networks.
Constructed with precision-engineered copper or aluminium conductors and high-grade PVC insulation, these cables provide optimal electrical performance, safety, and mechanical protection for fixed installations. They are suitable for a wide array of applications, including building wiring, supply to motors and transformers, lighting systems, socket outlets, and control circuits within switchgear and control panels.
RBICAB Low Voltage PVC Cables are tested and certified to meet rigorous international standards (IEC, IS, and equivalents) for low-voltage applications. Their design focuses on minimizing power loss, preventing overheating, and ensuring user safety through robust insulation that resists electrical, thermal, and mechanical stress.
Key advantages include safe operation for low-voltage systems, high efficiency in power delivery, robust construction for long-term reliability, flexibility in installation, wide acceptance in construction and industry, and full compliance with national and international electrical regulations.
Feature / Application | Details |
|---|---|
Conductor Material | High-purity copper or aluminium for excellent conductivity |
Cable Type | Armoured for mechanical protection; Unarmoured for indoor installations |
Insulation | PVC insulation for heat, moisture, and chemical resistance |
Voltage Rating | Suitable for low and medium voltage installations |
Current Carrying Capacity | As per conductor size and installation method |
Installation | Indoor, outdoor, industrial, residential, and commercial wiring |
Mechanical Protection | Armoured version protects against impact, rodents, and harsh conditions |
Standards Compliance | Manufactured as per IEC, IS, or equivalent standards |
Applications | Power distribution, lighting circuits, industrial plants, residential and commercial buildings |
Nominal Size of Cable | 3, 3.5 & 4 Core PVC Insulated & Sheathed Cables | ||
|---|---|---|---|
In Ground | In Air | Approx Voltage Drop | |
Amp | Amp | Mv/amp/mtr | |
16 | 61 | 52 | 4.00 |
25 | 78 | 70 | 2.50 |
35 | 94 | 85 | 1.80 |
50 | 111 | 104 | 1.30 |
70 | 136 | 131 | 1.00 |
95 | 163 | 156 | 0.68 |
120 | 185 | 186 | 0.54 |
150 | 206 | 212 | 0.43 |
185 | 234 | 245 | 0.38 |
240 | 271 | 291 | 0.28 |
300 | 305 | 335 | 0.25 |
400 | 348 | 390 | 0.20 |
Nominal Size | PVC Insulated | |
|---|---|---|
Copper | Aluminium | |
1.5 | 0.173 | - |
2.5 | 0.283 | - |
4 | 0.46 | 0.303 |
6 | 0.69 | 0.455 |
10 | 1.15 | 0.758 |
16 | 1.84 | 1.21 |
25 | 2.88 | 1.90 |
35 | 4.03 | 2.65 |
50 | 5.75 | 3.79 |
70 | 8.05 | 5.31 |
95 | 10.90 | 7.20 |
120 | 13.80 | 9.10 |
150 | 17.30 | 11.40 |
185 | 21.30 | 14.02 |
240 | 27.60 | 18.20 |
300 | 34.50 | 22.80 |
400 | 46 | 30.40 |
500 | 57.50 | 38 |
630 | 72.50 | 47.25 |
800 | 92 | 60 |
1000 | 115.00 | 75 |
D-18, Site-3, Meerut Road Industrial Area, UPSIDC, Ghaziabad, Uttar Pradesh 201003 (INDIA)